Skip to content
SAFETY GATEReference A12/00395/23

Drive — lesiones · security

Descriptive title organised by NagameAlert; the official wording is available from the source.

Official information organised for easier consultation. The source publication remains authoritative.

Identification

Product identification

Product
Drive
Brand
D+H Mechatronic AG
Category
Construction products
Lot/s
01.05.2022 - 30.11.2022
Product domain
Non-foodNagameAlert treatment

Official information

Risk and measures

Risk or hazard
Injuries · Security
Official description
A low quality cog (not hardened) has been installed in the chain drive. Under stress, it can break, hence the chain drive may no longer be able hold the smoke/heat extraction valve/window, and in the absence of other safety mechanisms installed, the valve/window can fall onto bystanders and injure them. The product does not comply with the Construction Products Regulation nor with the requirements of the General Product Safety Directive nor with the European standard EN 12101-2.
Measures
Type of economic operator taking notified measure(s): ManufacturerCategory of measure(s): Warning consumers of the risksDate of entry into force: 10/01/2023Type of economic operator taking notified measure(s): ManufacturerCategory of measure(s): Replacement of the defective chain driveDate of entry into force: 10/01/2023Type of economic operator taking notified measure(s): ManufacturerCategory of measure(s): Recall of the product from end usersDate of entry into force: 10/01/2023

Territory

Geography

Origin
Germany
Notifying country or territory
Germany
Distribution
Notificado por Germany

Provenance and context

NagameAlert distinguishes content published by the source from its organisation and normalisation. Values marked “NagameAlert” belong to that processing layer. Always check measures, scope and updates in the official publication.