Skip to content
OECDReference EN/KR/K20/EP/00044

Transformer and voltage regulator

Official information organised for easier consultation. The source publication remains authoritative.

Identification

Product identification

Product
Transformer and voltage regulator
Category
Converters/Inverters/Regulators/Transformers
Model
1000VA Down transformer DL-1000D
Product domain
Non-foodNagameAlert treatment

Official information

Risk and measures

Risk or hazard
ㅇ (Primary defect) ㅇ Temperature (heating line) rise exceeding the standard (Temperature rise test stopped due to fire in the middle of the test) - Maximum measured value: 152 ℃ - Allowable level: 100 ℃ ㅇ (Minor defect) ㅇ Insufficient labelling - Manufacturing year and month missing - Model missing - Type II appliance mark missing - IP marking missing ◇ Risk of fire during normal use due to excessive temperature rise ◇ Risk of providing wrong information
Recommendations
◇ Consumers who have it must stop using the product immediately. ◇ Contact and visit the place of purchase for exchange, refund or repair, etc.

Official information

Economic operators

Manufacturer
-

Territory

Geography

Origin
Korea (Republic of)
Distribution
Retirada en Korea (Republic of)
Country of recall
Korea (Republic of)

Provenance and context

NagameAlert distinguishes content published by the source from its organisation and normalisation. Values marked “NagameAlert” belong to that processing layer. Always check measures, scope and updates in the official publication.